Voltage Drop Calculator

Conductor
Circuit
V
A
ft

Distance from the panel to the load, not the round trip.

Voltage drop

6.18 V

Percent drop
5.15%
Voltage at load
113.8 V
Conductor resistance
1.93 Ω per 1,000 ft
Power lost in wire
99 W

Drop exceeds 3%. The NEC informational note recommends 3% max on a branch circuit and 5% total. Consider a larger wire.

All sizes at 16 A over 100 ft (copper)17 rows
SizeDrop (V)Drop (%)
1 AWG0.490.41%
2 AWG0.620.52%
3 AWG0.780.65%
4 AWG0.990.82%
6 AWG1.571.31%
8 AWG2.442.04%
10 AWG3.873.23%
12 AWG6.185.15%
14 AWG9.828.19%
250 kcmil0.160.14%
300 kcmil0.140.11%
350 kcmil0.120.1%
500 kcmil0.080.07%
1/0 AWG0.390.33%
2/0 AWG0.310.26%
3/0 AWG0.250.2%
4/0 AWG0.190.16%