Voltage Drop Calculator

Voltage drop and percent drop for copper or aluminum wire by AWG size, length and load current.

Conductor
Circuit
V
A
ft

Distance from the panel to the load, not the round trip.

Voltage drop

6.18 V

Percent drop
5.15%
Voltage at load
113.8 V
Conductor resistance
1.93 Ω per 1,000 ft
Power lost in wire
99 W

Drop exceeds 3%. The NEC informational note recommends 3% max on a branch circuit and 5% total. Consider a larger wire.

All sizes at 16 A over 100 ft (copper)17 rows
SizeDrop (V)Drop (%)
1 AWG0.490.41%
2 AWG0.620.52%
3 AWG0.780.65%
4 AWG0.990.82%
6 AWG1.571.31%
8 AWG2.442.04%
10 AWG3.873.23%
12 AWG6.185.15%
14 AWG9.828.19%
250 kcmil0.160.14%
300 kcmil0.140.11%
350 kcmil0.120.1%
500 kcmil0.080.07%
1/0 AWG0.390.33%
2/0 AWG0.310.26%
3/0 AWG0.250.2%
4/0 AWG0.190.16%

How it works

Every wire has resistance, so some voltage is lost along the run. Long runs at high current can leave motors, lights and chargers underpowered. This calculator uses DC resistance at 75 °C from NEC Chapter 9, Table 8.

For single-phase and DC circuits the current flows out and back, so the one-way length is doubled. For balanced three-phase circuits the multiplier is √3. Results ignore conductor reactance, which matters mainly for large conductors in steel conduit at AC.

Voltage drop is separate from ampacity. A wire can pass the voltage-drop check and still be too small for the breaker, so size for ampacity first (NEC 310.16), then upsize if the drop is too high.

Formula

Single-phase / DC: VD = 2 × L × I × R ÷ 1000 Three-phase: VD = √3 × L × I × R ÷ 1000 (L in feet, R in Ω per 1,000 ft)

Questions people ask

What voltage drop is acceptable?

NEC informational notes in 210.19 and 215.2 recommend no more than 3% on a branch circuit or feeder and 5% total from service to the farthest outlet. It is a recommendation, not a requirement, except in some special cases such as fire pumps.

Should I enter the round-trip length?

No. Enter the one-way distance from the panel to the load. The calculator doubles it for single-phase and DC circuits and applies √3 for three-phase.

Why is aluminum drop higher?

Aluminum has about 61% of the conductivity of copper, so the same gauge has roughly 1.6 times the resistance. Aluminum is usually upsized by about two AWG sizes to match copper.

Does temperature matter?

Yes. Copper resistance rises about 0.39% per °C. These values assume 75 °C conductors, which is conservative for lightly loaded circuits in cool locations.